SMOKE ALARMS
Queensland: 2022 Legislation Requirements
DWELLINGS BEING SOLD, LEASED OR AN EXISTING LEASE IS RENEWED
From 1 January 2022
Smoke alarms in the dwelling must:
i) be photoelectric (AS 3786-2014); and
ii) not also contain an ionisation sensor; and
iii) be less than 10 years old; and
iv) operate when tested; and
v) be interconnected with every other smoke alarm in the dwelling so all activate together.
Smoke alarms must be installed on each storey:
i) in each bedroom; and
ii) in hallways which connect bedrooms and the rest of the dwelling; or
iii) if there is no hallway, between the bedrooms and other parts of the storey; and
iv) if there are no bedrooms on a storey at least one smoke alarm must be installed in the most likely path of travel to exit the dwelling.
Smoke alarms must be hardwired or powered by a non-removable 10-year battery, or a combination of both may be allowed.