Queensland: 2022 Legislation Requirements

DWELLINGS BEING SOLD, LEASED OR AN EXISTING LEASE IS RENEWED

From 1 January 2022

Smoke alarms in the dwelling must:

 

i) be photoelectric (AS 3786-2014); and

ii) not also contain an ionisation sensor; and

iii) be less than 10 years old; and

iv) operate when tested; and

v) be interconnected with every other smoke alarm in the dwelling so all activate together.

 

Smoke alarms must be installed on each storey:

 

i) in each bedroom; and

ii) in hallways which connect bedrooms and the rest of the dwelling; or

iii) if there is no hallway, between the bedrooms and other parts of the storey; and

iv) if there are no bedrooms on a storey at least one smoke alarm must be installed in the most likely path of travel to exit the dwelling.

 

Smoke alarms must be hardwired or powered by a non-removable 10-year battery, or a combination of both may be allowed.

 